Warom

WAROM Technology MENA FZCO

Total, custom solution provider, offering full scope of WAROM brand and services to our clients in the Middle East and North Africa, with singular focus on the needs of our client

Plot No.S10103, Jebel Ali Free Zone,
Dubai, UAE, P.O.Box 263667

Back to top

BAY51-D Series

Explosion-proof Light Fittings for Fluorescent Lamp

  • Explosion protection compliant with CENELEC, IEC, and NEC standards
  • Suitable for hazardous areas:
    • Zone 1 and Zone 2
    • Zone 21 and Zone 22
    • Class I, Zone 1 and Zone 2
    • Class I, Division 1, Groups B, C, D
  • Available in three enclosure types:
    • Type I
    • Type II
    • Type III
  • Available lamp configurations:
    • Type I: T8 18W ×2, LED 9W ×2
    • Type II: T8 36W ×2, LED 18W ×2
    • Type III: T8 58W ×2, LED 28W ×2
  • Optimized luminous flux for improved lighting performance
  • Glass tube designed to withstand 4J impact
  • Enclosure made from copper-free aluminium alloy, powder-coated (RAL1021), corrosion-resistant
  • Built-in electronic ballast with wide voltage input, rapid start, stable performance, and power factor ≥ 0.95
  • Built-in LED driver with CC-CV (constant current–constant voltage) output, power factor ≥ 0.95
  • End-of-lamp-life (EOL) rectification effect protection
  • Emergency function available on request
Explosion protection
Global (IECEx)

IECEx CQM 11.0022X

Gas and dust

Ex db IIC T6 Gb
Ex tb IIIC T80°C Db

Europe (ATEX)

CNEX 21 ATEX 0001X

Gas and dust

II 2 G Ex db IIC T6 Gb
II 2 D Ex tb IIIC T80°C Db

Certificates

IECEx; ATEX; CU-TR

Conformity to standards

EN 60079-0, EN 60079-1, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-31

Enclosure material

Copper-free Aluminium Alloy or cast iron, powder coated surface

Enclosure colour

Yellow (RAL1021)

Exposed fastener

Stainless steel

Rated current

≤20A

Rated voltage

Max. 690V AC 50/60Hz, Max. 500V DC

Terminal data Number

6 terminals (Type A-E), 4 terminals (Type F)

Cross section of cable

0.2~2.5mm²

Degree of protection

IP66

Ambient temperature

-60°C~+60°C

Internal & external earthing

M5

Cable entries

Standard M□×1.5 plug
NPT□ plug on request

Cable gland (optional)

DQM-II (Ex d) or DQM-III (Ex d) is recommended. Please see P6/24~39.

Main application

Type A-E are used for wiring or branching;