Warom

WAROM Technology MENA FZCO

Total, custom solution provider, offering full scope of WAROM brand and services to our clients in the Middle East and North Africa, with singular focus on the needs of our client

Plot No.S10103, Jebel Ali Free Zone,
Dubai, UAE, P.O.Box 263667

Back to top

BXJ95 Series

Explosion-proof High-voltage Junction Boxes

● Explosion protection to

  • CENELEC
  • IEC
  • NEC

● Can be used in
Zone 1 and Zone 2
Zone 21 and Zone 22
Class I, Zone 1 and Zone 2
Class I, Division 1, Groups B, C, D

● Flameproof enclosure (Ex d IIB+H₂), which can be used as feed distribution equipment in control and distribution systems (such as distribution box, switch box of main circuit, control box, terminal box or motor starting box etc.)

● Copper-free Aluminium Alloy enclosure, powder coated surface

● Equipped with specialized hinge structure, which can prevent the flameproof joints from damage when opening and closing the box, and greatly prolong the service life of box

● The boxes can be combined and installed freely to save space and meet the requirements of various distribution systems

● Special requirements on request

● The large space of the enclosure makes it easy for wire assembling

● Adopting high-precision machining, excellent explosion-proof performance

● Professionally designed door handles, reliable and safe when opening the door

● Professionally designed hinges, reliable and safe when opening the door

Explosion protection
Global (IECEx)

IECEx PCET 24.0030X

Gas and dust

Ex db IIB+H₂ T6/T5 Gb
Ex tb IIIC T80°C/T95°C Db

Europe (ATEX)

ACE 25 ATEX 033X

Gas and dust

II 2 G Ex db IIB+H₂ T6/T5 Gb
II 2 D Ex tb IIIC T80°C/T95°C Db

Certificates

IECEx; ATEX

Conformity to standards

EN 60079-0, EN 60079-1, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-31

Enclosure material

Copper-free Aluminium Alloy enclosure, powder coated surface, window grey (RAL7040)

Exposed fastener

Stainless steel

Rated voltage

Max. 15kV AC

Rated current

Max. 800A

Degree of protection

IP66

Internal & external earthing

M8/M8

Ambient temperature

T6/T80°C for Tamb: -60°C ~ +40°C
T5/T95°C for Tamb: -60°C ~ +60°C

Cable entries

Standard M□×1.5 plug (the size of entry hole should be processed in accordance with actual requirements), NPT plug on request

Cable gland (optional)

DQM-II (Ex d) or DQM-III (Ex d) is recommended. Please see P6/24~39

Entry direction

Bottom

Mounting

Surface type (standard)
Pedestal type (optional)