BAT86 Series

Explosion-proof LED Floodlights

  • Explosion protection compliant with CENELEC, IEC, and NEC standards
  • Suitable for hazardous areas:
    • Zone 1 and Zone 2
    • Zone 21 and Zone 22
    • Class I, Zone 1 and Zone 2
    • Class I, Division 1, Groups A, B, C, D
  • Available in three enclosure sizes:
    • 90
    • 160
    • 240
  • Applicable LED power options (up to 240W):
    • 60W, 90W, 120W, 160W, 200W, 240W
  • Optimized luminous flux for improved lighting performance
  • Isolated LED lamp compartment with CC-CV (constant current–constant voltage) control system
  • Separate compartments for lamp, power supply, and terminals for enhanced safety and reliability
  • Efficient heat dissipation through wind-convection structure
  • Standard configuration without lens, providing floodlight distribution
    • Optional lenses available: 30° and 60° beam angles
  • 240-type fittings support dual-lamp configuration:
    • Total output up to 2 × 200W or 2 × 240W
  • Updated mechanical design including bracket and mounting structure for improved installation flexibility
  • Product weight and structural design optimized for durability and handling
  • Low maintenance design with service life up to 100,000 operating hours
Explosion Protection

IECEx (Global)

  • Ex db IIB+H₂ T* Gb
  • Ex tb IIIC T* Db

ATEX (Europe)

  • II 2G Ex db IIB+H₂ T* Gb
  • II 2D Ex tb IIIC T* Db
Certifications & Standards
  • IECEx, ATEX, CU-TR, INMETRO
  • EN 60079-0 / -1 / -7 / -28 / -31
  • IEC 60079-0 / -1 / -7 / -28 / -31
Construction & Materials
  • Enclosure: Copper-free aluminium alloy, powder-coated (RAL1021), corrosion-resistant
  • Glass Cover: Toughened glass, 4J impact resistant
  • Fasteners: Stainless steel
  • LED Driver:
    • Wide voltage input
    • CC-CV (constant current–constant voltage) output
    • Power factor ≥ 0.95
    • Protection against overcurrent, open circuit, short circuit, surge, and EMI
Light Source
  • Type: Integrated multi-LED module
  • Power Options:
    • 60W, 90W, 120W, 160W, 200W, 240W
  • Optimized luminous flux for improved lighting performance
  • CRI (Ra): ≥ 70 / ≥ 80 (depending on model)
  • CCT: 5700K
    • Optional: Warm white / Natural white
Electrical Data
  • Voltage:
    • 100–277V AC, 50/60Hz
    • 130–250V DC
  • Earthing: M5 (internal & external earth bolts)
Protection & Environment
  • Ingress Protection: IP66
  • Ambient Temperature:
    • -60°C to +60°C (varies by wattage and classification)
Installation
  • Terminals: 3 × 1.5–4 mm² (L + N + PE)
  • Mounting Options:
    • Fixed type
    • Bracket type
    • Street lamp type
Cable Entry
  • Cable Entry:
    • 2 × M25 ×1.5 plugs
  • Cable Gland:
    • DQM-II (Ex d) recommended
Optical System
  • Standard configuration provides floodlight distribution (no lens)
  • Optional lenses available:
    • 30° beam angle
    • 60° beam angle