Warom

WAROM Technology MENA FZCO

Total, custom solution provider, offering full scope of WAROM brand and services to our clients in the Middle East and North Africa, with singular focus on the needs of our client

Plot No.S10103, Jebel Ali Free Zone,
Dubai, UAE, P.O.Box 263667

Back to top

G☐-WRS

Point-type Toxic /Combustible Gas Detectors for Industrial and Commercial (Catalytic Combustion Type)

• Explosion protection to
– CENELEC
– IEC

• Can be used in
– Zone 1 and Zone 2
– Zone 21 and Zone 22

• Explosion-proof design with flameproof enclosure, suitable for indoor and outdoor explosive gas and dust environments, ensuring safety and reliability

• LCD or LED digital screen for on-site concentration display, with LED indicators for status: “Normal” (green), “Fault” (yellow), and “Alarm” (red)

Explosion protection

Global (IECEx)
Gas and dust
IECEx NEP 25.0081X
Ex db IIC T6 Gb
Ex tb IIIC T80°C Db

Europe (ATEX)
Gas and dust
ATEX (applied for)
II 2 G Ex db IIC T6 Gb
II 2 D Ex tb IIIC T80°C Db

Certificates

IECEx; ATEX

Conformity to standards

IEC 60079-0, IEC 60079-1, IEC 60079-31
EN 60079-0, EN 60079-1, EN 60079-31

Power supply

Systematic: 3.7, 12, 24VDC
Standalone: 220VAC

Power consumption

<3W

Output signal

Three-wire system: 4–20mA/RS485 (MODBUS protocol), optional relay output function

Inlet specification

M20×1.5 internal, optional NPT1/2

Transmission method

4G, 5G, NB-IoT, LoRaWAN, etc.

Gas to be detected

Combustible gases (refer to the list of combustible gases)

Detection principle

Catalytic combustion type

Measurement range

(3–100)%LEL

Accuracy

±3%LEL

Repeatability

≤2%

Protection rating

IP65/IP66

Temperature range

-40°C~+55°C / -40°C~+70°C

Humidity range

<95% (no condensation)