BXM(D)53 Series

Explosion-proof Illumination (Power) Distribution Boxes (Ex d e IIC)

  • Explosion protection to
    • CENELEC
    • IEC
    • NEC
  • Can be used in
    • Zone 1 and Zone 2
    • Zone 21 and Zone 22
    • Class I, Zone 1 and Zone 2
    • Class I, Division 2, Groups A, B, C, D
  • Enclosure for modular combination (Ex d & Ex e)
  • Main switch and branch switch are operated with external rotary actuator
  • Internal wiring to the terminal is finished
  • International brand of explosion-proof terminal blocks
  • Copper-free Aluminium Alloy, powder coated surface
  • Entries plugged. Cable glands on request (see P7/17~19)
  • Special requirements on request

Explosion protection
Global (IECEx) – Gas and dust
IECEx CQM 11.0042X
Ex db eb IIC T6 Gb
Ex tb IIIC T80°C Db IP66

Europe (ATEX) – Gas and dust
TÜV CY 18 ATEX 0206016X
II 2 G Ex db eb IIC T6 Gb
II 2 D Ex tb IIIC T80°C Db IP66

Certificates / Conformity to standards
IECEx; ATEX; CU-TR
EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-31

General power supply
Rated voltage: max. 690V AC 50/60Hz
Rated current: max. 100A
Branch current: 1A, 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A

Exposed fastener
Stainless steel

Enclosure
Enclosure material: Copper-free Aluminium Alloy, powder coated surface
Enclosure colour: Window grey (RAL7040)
Enclosure type: Modular combination (Ex d & Ex e); MCB, MCCB or other components in Ex d compartment, explosion-proof indicators and terminals in Ex e compartment

Built-in components
Main switch: MCB (miniature circuit breaker) or MCCB (moulded case circuit breaker)
Note: earth leakage protection on request

Branch switch: MCB (miniature circuit breaker) or MCCB (moulded case circuit breaker)
Note: earth leakage protection on request

Terminal: International brand of explosion-proof terminal blocks
Indicator: Red

Degree of protection
IP66

Internal & external earthing
M6/M8

Ambient temperature
-40°C ~ +55°C

Cable entries
Standard M□×1.5 plug (see the Selection table on P5/14)

Cable gland (optional)
DQM-II (Ex eb) is recommended. Please see P6/20~23

Entry direction
Bottom

Mounting
Surface type (standard)